Customization: | Available |
---|---|
Theory: | Electromagnetic Relay |
Usage: | Insulation Monitor |
Still deciding? Get samples of US$ 70/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
GYDCG-UBCS1 Series is a DC insulation monitoring device based on MODBUS protocol, including DC-to-ground insulation impedance monitoring, DC voltage monitoring, DC voltage reverse connection alarm, and other safety monitoring functions. It can be used for electric vehicle DC charging systems, photovoltaic systems, energy storage systems, DC grids, and other DC systems below 1000V.
Basic parameters
Parameter | Value | ||
Power supply | 10-30VDC, Power 3w | ||
DC voltage range | 100V~1000V | ||
DC voltage measurement accuracy |
≤2V+0.3% | ||
Insulation resistance measurement range |
1KΩ~10MΩ (DC System voltage:100V~1000V) |
||
Insulation monitoring accuracy ((When :DC voltage:100V-1000V) |
CY range | Resistance range | Accuracy |
0~0.8μF | ≤60kΩ | ≤3kΩ | |
60kΩ<R≤1MΩ | ≤5% | ||
0.8μF ~3μF | ≤60kΩ | ≤6kΩ | |
60kΩ<R≤1MΩ | ≤20% | ||
Off-line pressure test | <2mA | ||
Standard | IEC 61851-23 (2014-03):2014-11 | ||
Humidity | 85% | ||
Storage temperature | - 40°C ~125°C | ||
Operating temperature | - 40°C ~75°C |