HVD high voltage indicator is adapted for indoor electrical panels, used in MV / HV switchgear. It is connected via internal wiring to capacitive sensors inside the switchgear. Rated voltage 3~40.5kv, operation frequency 50Hz network to display the electrifying situation of the high voltage loop where the device is mounted.
This integrated voltage-detecting system is used for continuous operation. The condition "voltage present" is displayed by three LED indicators.
ated voltage: | 24V/110V/220V |
Voltage level | 1..52 kV (Medium-voltage) |
Contact capacity (Passive) | 8A,250VAC/48VDC |
Power consumption | <2W |
Working frequency | 50Hz/60Hz |
Standard | IEC 61243-5 IEC 62271-213 |
Insulation strength | 2kV,1min |
Nominal Voltage |
3-3.6kV |
6-7.2kV | |
10-12kV | |
20-24kV | |
35-40.5kV | |
Shielded Cable Length | 2M,or customized by buyers |
Threshold Values for Voltage Presence Indication | U>0.40 x Unmin |
Threshold Values for Voltage Absence indication | U<0.15 x Unmin |
Threshold Values for Over-voltage Protection | U<0.30 x Unmin |
Front display | LCD/LED Display |
Controls | Self-test button |
Operating temperature | -25°C … 55°C, RH<95%, Altitude: ≤1000m |
Storage temperature | -30°C … 75°C, RH<95% |
Protection class | IP40/IP65 |
Type of interface | LRM |
Lifetime | Minimum 31 years (MTBF) |
Mounting Dimension (WxHxD) |
Panel window size 92x45mm