1. Have microcontroller technology as the core, using the latest algorithms, to achieve precise measurement.
2. The current transducer transmitter converts an AC input into a load-independent output signal.
3. The three-phase voltage transducer has excellent temperature characteristics and good working stability.
4. The output signal is based on the root mean square(rms) measurement of the input signal and hence the transducer can be used
with distorted waveforms.
5. The unit conforms to IEC 60688. In addition, the 3-phase voltage transmitter meets the insulation requirements of IEC
60255-5, clauses 5, 6, and 8 as well as the high-frequency disturbance test of IEC 60255-22 for Class III test voltage.
Inputs:
System current 1A, 5A, 10A, 30A
Absorbed power 0.3VA
Frequency range 50Hz, 60Hz
Output:
Standard nominal outputs 4~20mA, 0-5V,
(others on request) 0-20mA, 5-10V 0-10V
Ripple <0.5% peak to peak
Load Resistance Current output: 0<1kΩ;
Voltage output: Lr>5KΩ
Accuracy:
Class 0.5 to IEC 60688 0.5%of nominal output for specified range
Accurate range 0 - 120% I
Frequency influence <0.02% per Hz
Load influence <0.25% of full span for specific load range
Auxiliary Supply: 48V, 110V, 230/240V AC 20%, 1.5VA
24V, 48V, 110V DC 20% 2W
Isolation: Galvanic isolation between input, output circuits and auxiliary supply
Test voltage 2KV RMS 50Hz for 1 minute
impulse 4KV 1.2/50µsec waveform
Temperature:
Operating -10~55C
Storage -40~70C, 20 ~ 93%RH ; Noncondensing