Customization: | Available |
---|---|
Type: | Electromagnetic |
Output Signal Type: | Digital Output |
Still deciding? Get samples of US$ 110/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Electrical Signal Inputs
|
|
|
Nominal input
|
1 or 5 Amp C.T. connected
|
|
|
110V, 230V, 240V, 400V, 415V ac +/-20%
|
|
Power consumption
|
<1 VA voltage
|
|
|
<0.2 VA current
|
|
Overload capacity
|
1.2 times continuous
|
|
|
5sec @ 10 times of rated current
2sec @ 2 times of rated voltage |
|
Frequency range
|
40~65Hz
|
|
Measurement Output
|
|
|
Standard outputs
|
4~20mA/ 0-20mA programmable
(0~5V / 0~10V optional) |
|
Maximum load
|
<390 Ω (current output)
>10KΩ (voltage output) |
|
Ripple
|
<1% peak to peak
|
|
Response time
|
<350ms 0-90%
|
|
|
<500ms 0-99%
|
|
Measurement Accuracy
|
|
|
Class
|
0.2% / 0.5 complying with IEC 60688
|
|
Accurate range
|
0 - 120% I
|
|
Frequency influence
|
<0.05% per Hz
|
|
Load influence
|
<0.25% of F.S. for specific load range
|
|
Auxiliary Supply
|
|
|
Rating
|
85-265Vac/dc,
Optional 12V, 24V, 48VDC |
|
Consumption
|
<3VA
|
|
Galvanic isolation between I/O and AUX
|
|
|
Test voltage
|
2KV RMS 50Hz for 1 minute
|
|
impulse
|
4KV 1.2/50µsec waveform
|
|
Temperature requirements
|
|
|
Operating
|
-10~55
|
|
Storage
|
-40~70, 20 ~ 93%RH ; Noncondensing
|