Customization: | Available |
---|---|
After-sales Service: | 1 Year |
Warranty: | 1 Year |
Still deciding? Get samples of US$ 200/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make at Made-in-china.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The MCM263T branch circuit power meter is a high-performance energy measurement device designed for the industrial system or equipment. This multi-circuit energy meter takes measurements from 6xthree-phase circuits or 18xsingle-phase circuits. 5A CT connection is supported by default, and 100mA CT is optional for different current measurement requirements.
With multi-communication interface, various I/O, option, it can realize efficient data transmission and remote monitoring, and meet various network environments. Whether in large industrial facilities or complex power systems, the MCM263T can provide accurate energy measurement and comprehensive management solutions, making it an ideal choice for industrial branch circuit power monitoring.
Working Power
AC/DC 90-240V, 45-65Hz, or DC 20-60V (Optional)
Maximum power consumption 6W
Input
Current: | Rated 5A (Optional 1A) |
Voltage: | Rated 0~480V (CATIII-300V) |
Frequency: | 45-65Hz |
Current overload : | 1.2 times rated continuous; 5 seconds for 10 times of the rated |
Voltage overload : | 30 seconds for 2 times of the rated |
Parameter | Accuracy | A phase | B phase | C phase | All |
Voltage Current Active Power Reactive Power Apparent power Power Factor Active Energy Reactive Energy Frequency |
0.2 0.2 0.5 0.5 0.5 0.5 1 2 0.1 |
V1 A1 W1 var1 VA1 PF1 |
V2 A2 W2 var2 VA2 PF2 |
V3 A3 W3 var3 VA3 PF3 |
W var VA PF Wh varh Hz |
Parameter | Standard | Test voltage |
Discharge immunity test | IEC61000-4-2 level 4 | 8kV |
Surge (Shock) immunity test | IEC61000-4-5 level 4 | Common test voltage 4kV |
Fast transient burst immunity test | IEC61000-4-4 level 3 | Input 1kV; Power supply 2kV |
Basic Electricity | IEC 61557-12:2018 |
Active energy | IEC 62053-21:2020 |
Reactive energy | IEC 62053-23:2020 |
Exhibition photo display