value
|
Model Number
|
CE-IJ31-DS5-0.5
|
Type
|
Current transducer
|
Place of Origin
|
Zhejiang
|
Usage
|
Industry, railway, electricity
|
Theory
|
The principle of electromagnetic isolation
|
Output
|
05V ,020mA,420mA, 010Voptional
|
Model
|
CE-IJ31-DS5-0.5
|
Power supply
|
12VDC, 15VDC, 24VDC, 220VAC (optional)
|
Input range
|
0~200A AC
|
Output
|
05V ,020mA,420mA, 010Voptional
|
Ambient temperature
|
-10°C+60°C
|
Accuracy
|
0.5
|
Load Capacity
|
Voltage output load ≥ 1KΩ,
Current output load ≤ 300Ω |
Temperature drift
|
≤300PPm/°C
|
Isolation voltage
|
DC 2500V
|
Response time
|
≤300 mS
|
Rated power consumption
|
≤1W, ≤2W
|
Output ripple
|
≤10mV
|
Frequency range
|
45~65Hz
(up to 5K, please specify when ordering) |
Surge impact immunity
|
Power port level± 0.5KV (L-N / 2Ω / integrated)
Analog I / O port a ± 0.5KV (L-N / 40Ω / integrated wave) |
Impulse immunity
|
Input/power port ± 2KV
Analog I / O port ± 1KV |
Input overload capacity
|
20 times the nominal value of the measurement current (maximum 500A),
(Apply a repetition of five times a second, interval 300s); |
Operating temperature
|
-20+70
|
Storage temperature & Humidity
|
-55 ~+65°C;
humidity: ≤95% (no dew) |