Customization: | Available |
---|---|
Theory: | Voltage Relay |
Usage: | Motor Relay |
Still deciding? Get samples of US$ 150/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Protection Function | Start timeout, overload, overcurrent stall, phase failure, current unbalance, short circuit, underload, temperature, restart, overflow fault (fault current contactor breaking capacity) tripped circuit breaker |
Optional protection function | Ground leakage, overvoltage, Undervoltage, frequency, underpower factor, TE protection, anti-shock |
Connection method | Extention type |
Programmable operating modes | Protection mode, direct start mode, two-way reversible start mode, two-relay mode, two-speed click start mode, circuit breaker direct start mode |
Communication interface | 1 RS485 interface, communication protocol Modbus-RTU; optional 2 RS485 interfaces, optional Profibus-DP interface |
Switch input | 10 DI |
Relay output | 5-way DO |
Optional Analog input | 1-2 channels DC 4-20mA analog output, programmable parameters |
Measurement display | three-phase current, ground leakage current, three-phase current unbalance rate, heat capacity, thermal resistance, three-line voltage, frequency, power factor, active power, reactive power |
Fault record | a maximum record of 99 words of recent fault information, resolution IS |
Statistical information | record the total running time, total parking time, number of stops, and number of trips of the motor |
Under-voltage and voltage-loss restart | realize short-term under-voltage and voltage-loss restart functions |
The working environment of PR 240 Intelligent Motor Management Relay
Motor-rated voltage: | AC380V / AC660V |
Motor rated current: | 0.5-820A |
Working temperature: | -10C ~ +55C |
Storage temperature: | -25C ~ +70C |
Relative humidity: | < 93% RH |
Elevation: | not more than 3000 m |
Atmospheric conditions: | installation site does not allow the explosive medium, containing gas to corrode metal and damage the insulation and conductive medium. |
Measuring the accuracy of PR 240
Current: | ± 0.5% @ 10% to 200% of Ie |
Voltage: | ± 0.5% @ 10%~150%Ue |
Frequency: | ± 0.1% @ 45 ~ 65Hz |
Power factor: | ± 1.0% @ 0 ~ 1.000 |
Active Power | ± 1.0% @ 0 ~ 500kW |
Leakage current: | ± 1% @10% to 100% of Ir |
Analog Output: | ± 1% @4 ~ 20mA |
Electrical parameters of PR 240 Motor Protector
Auxiliary Power: | AC90-240Vac/dc |
Power consumption: | <10 VA |
Insulation resistance: | > 100MΩ |
Relay: | Alarm relay @ 5A / 250VAC, 5A / 30VDC (NO node) |
Electrical test of PR 240 Motor Protection Relay:
IEC 61000-4-2 | level III |
IEC 61000-4-4 | level III |
IEC 61000-4-5 | level III |
IEC 61010-1 | AC2kV/1min Between power/input / output |