Customization: | Available |
---|---|
Theory: | Electromagnetic Relay |
Usage: | Partial Discharge Monitor |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
PDG-1000 continuously monitors partial discharge (PD) in equipment such as transformers, cables in switchgear rotating machines, etc.
It analyzes RF emissions in the HF, VHF, and lower UHF ranges by sensors outside the cabinet. HMI unit provides site display of TEV amplitude, ultrasonic amplitude, DO port can drive local alarms, Multi-level alarm notice site engineer. PDG-1000 also can communicate data and notifications across standard RS485 Modbus interface to networked supervisory systems.
HMI electrical parameters of PD monitoring for switchgear:
Auxiliary Power | 85-265Vac/dc |
20-60Vdc Optional | |
Power consumption | <6W |
Communication | RS-485, MODBUS-RTU |
Digital output | 2* NC & NO, passive node |
Enviorment temperature | -10 ~ +60°C |
Enviorment humidity | RH 20% ~ 95% (No condensation) |
Dimensions (L × W × H) | 144*144*100mm |
Open install hole | 138*138mm |
Remote sensor common:
Power supply | 12Vdc or 2000mAh build in battery* |
Wireless band* | 433Mhz ~2.4Ghz optional |
Signal transmission distance | Up to 80m (260 feet) |
Static power consumption | <10mW |
Installation method | 4* strong magnet, wall mount |
TEV sensor:
Detect range | 0~60 dBmV |
HF Frequency Response | 3~100MHz |
Resolution / Accuracy | 1dBmV / ±1dBmV |
Ultrasound sensor:
Detect range | -7dBμV ~ 68dBμV |
Resolution / Accuracy | 1dB / ±1dB |
Sensitivity | -65 dB (0 dB=1 volt/μbar rms SPL) |
Sensor Center Frequency | 40 kHz |